1WR-Temp Rack19 2p
011-Wire temperature sensor for 19 inch racks, two RJ11 ports for daisy-chaining
- Measuring range-10 to +80 °C
- Accuracy±0.8 °C in whole range, resolution 0.10
- Interface1-Wire, 2x RJ11, 5 V, 3m cable
- ProtectionIP30, 44 × 84 × 19 mm
I sit in a 19 inch rack and measure -10 to +80 °C. My two RJ11 ports let you chain the next sensor from me.
1WR-Temp IP67
02Stainless steel 1-Wire temperature probe with IP67 protection, in 1 m, 3 m or 10 m lengths
- Measuring range-10 to +80 °C
- Accuracy±0.8 °C, resolution 0.10
- Cable length1 m / 3 m / 10 m
- Interface and protection1-Wire (RJ11, 5 V), IP67
I am the general purpose probe: stainless steel, IP67, immersible to 1 m. You pick a 1 m, 3 m or 10 m cable.
1WR-Temp Flat 3m
03Stainless steel temperature probe with a flat cable that routes under a fridge door seal
- Measuring range-30 to +60 °C
- Accuracy±0.8 °C from -10 to +60 °C, ±2.0 °C in whole range
- Cable length3m, flat connection cable
- Interface1-Wire (RJ11, 5 V / 1 mA)
My flat cable slips under a refrigerator or freezer door seal. The stainless steel probe measures -30 to +60 °C.
1WR-Temp Outdoor 3m
04Outdoor 1-Wire temperature probe, stainless steel IP67 casing, -50 to +125 °C
- Measuring range-50 to +125 °C
- Accuracy±0.8 °C from -10 to +80 °C, ±2.0 °C from -30 to +125 °C
- Cable length3m PVC cable
- Interface and protection1-Wire (RJ11, 5 V / 1 mA), IP67
I go outside. My stainless steel casing is IP67 and I read from -50 to +125 °C, so frost and heat are both fine.
1WR-Humid
05Humidity-only 1-Wire probe for IT racks, 0 to 100 % RH, 1 m or 3 m cable
- Measuring range0 to 100 % RH
- Accuracy5 % RH (0 to 100 % RH non-condensing, 25 °C), linearity ±2.0 % RH
- Cable length1m / 3m
- Interface and protection1-Wire (RJ11, 5 V), IP65
I only measure relative humidity, 0 to 100 % RH. Clip me to a cable bundle in a rack and I report over 1-Wire.
1WR-HTemp 3m
06Combined 1-Wire temperature and humidity rod sensor for indoor and outdoor use
- Temperature-30 to +80 °C, ±0.8 °C from 0 to +60 °C
- Humidity0 to 100 % RH, 5 % RH (non-condensing, 25 °C)
- Cable length3m
- Interface and protection1-Wire (RJ11, 5 V), IP40
I give you two values from one RJ11 port, temperature and relative humidity. I am a slim rod, 78 × 10 × 6 mm.
1WR-HTemp Rack19 2p
071U rack temperature and humidity probe with two RJ11 ports for daisy-chaining
- Temperature-10 to +80 °C, ±0.8 °C
- Humidity0 to 100 % RH, 5 % RH (2 to 80 % RH non-condensing, 25 °C)
- Interface1-Wire, 2x RJ11 daisy-chainable, 3m cable included
- ProtectionIP23, 44 × 84 × 19 mm
I am the rack version with both values. Mount me as a 1U device at the front or back and chain the next sensor through my second port.
1WR-HTemp Outdoor 3m
08Outdoor temperature and humidity probe on the 1-Wire bus, IP64, 3 m cable
- Temperature-30 to +85 °C, ±0.8 °C
- Humidity0 to 100 % RH, 5 % RH (2 to 80 % RH non-condensing, 25 °C)
- Cable length3m
- Interface and protection1-Wire (RJ11, 5 V / 1 mA), IP64
I measure temperature and humidity outdoors. IP64 probe, 15 mm across and 112 mm long, on a 3 m cable.
HTemp-1Wire-Box2
09Wall mount temperature and humidity sensor box with two RJ11 ports
- Temperature-10 to +80 °C, ±0.8 °C
- Humidity0 to 100 % RH, 5 % RH (2 to 80 % RH non-condensing, 25 °C)
- Interface1-Wire, 2x RJ11, 5 V / 1 mA, 3m cable included
- ProtectionIP30, 79 × 71 × 30 mm
I am the wall box for offices and storage rooms. Two RJ11 ports let you daisy-chain, and a 3 m cable comes with me.
1WU HTemp B1
10Small 40 × 40 mm indoor temperature and humidity box with RJ11 (1WU) interface
- Temperature-40 to 85 °C, ±0.5 °C, resolution 0.1 °C
- Humidity0 to 100 % RH, 5 % RH / 25 °C
- InterfaceRJ11 (1WU), bus up to 60 m, 3-meter RJ11 cable included
- ProtectionIP30, 40 × 40 × 20 mm
I am the small 4 by 4 cm box. Stick me to a wall, ceiling or desk with tape and I report temperature to ±0.5 °C plus humidity.
Temp-1Wire Pt100
11Industrial Pt100 temperature probe, -50 to +200 °C, IP67, 8-point calibration
- Measuring range-50 °C to +200 °C
- Accuracy±(0,25 + 0,002|t|), resolution 0.10 °C, calibration in 8 points
- Cable length3m
- Interface and protectionRJ11 (1Wire or 1Wire UNI), IP67
When you need industrial precision, I am the Pt100 probe. -50 to +200 °C, IP67, and I can be calibrated at 8 points.
1WU-Temp Pt100 Frost 3m
12Cryo Pt100 temperature probe, -200 to +160 °C, IP67, 8-point calibration
- Measuring range-200 °C to +160 °C
- Accuracy±(0,25 + 0,002|t|), resolution 0.10 °C, calibration in 8 points
- Cable length3m
- Interface and protectionRJ11 (1Wire or 1Wire UNI), IP67
I am the cryo version. -200 to +160 °C with the same Pt100 precision and IP67 protection.
Temp-1W-UNI Pt100 Cable
13Pt100 probe on a 2 m silicon cable with a 1-Wire UNI converter, second probe input free
- Measuring range-50 to +200 °C (probe only)
- Accuracy±0.3 °C in whole range, resolution 0.10, 8 calibrated points
- Cable length2m silicon cable, probe IP67
- Interface1-Wire UNI (RJ11, 5 V / 20 mA)
I combine a Pt100/A probe with the 2xPt100 converter on the cable, ±0.3 °C in the whole range. You can add a second Pt100 or Pt1000 probe to me.
Converter 2xPt100 1W-UNI
14Connects one or two Pt100 or Pt1000 probes to the 1-Wire UNI bus, 2, 3 or 4-wire
- Measuring range-200 to +850 °C (Pt-100), 2-wire, 3-wire or 4-wire probes
- Accuracy±0.3 °C up to +650 °C, ±0.6 °C up to +850 °C (at +25 °C converter temperature)
- Interface1Wire-UNI, 2x RJ11 daisy-chain, max. 60m, bus powered
- Calibration8 points, 65 x 80 x 30 mm
Bring your own Pt100 or Pt1000 probes and I put them on the 1-Wire UNI bus. I detect the probe type myself and cover -200 to +850 °C.
HWg HTemp-485 T3411 / T3419, HWg PHTemp-485 T7410
15RS-485 temperature and humidity sensors with LCD display, T7410 also measures pressure
- TemperatureT3411 and T7410: -30 to +80°C, T3419: -30 to +105°C, accuracy ±0.4°C
- Humidity0 to 100%, ±2.5%RH (5 to 95% / 23°C)
- InterfaceRS-485 (HWg-Poseidon protocol, 9600 8N1), up to 1000m, power 9..30V / 0.5W
- ProtectionProbe IP40, box IP65 (IP54 for T7410)
I talk RS-485 to a Poseidon unit over up to 1000 m and show my values on a display. Several of me can share one line.